QUINT-UPS/ 24DC/ 24DC/10
13
Servicing
To switch to service mode, the following options are available:
– Button on the front of the UPS
– UPS-CONF software
– Service stick
Details can be found in the UPS-CONF user manual at
www.phoenixcontact.net/catalog .
Replacing the battery
?
Press and hold down both buttons on the front of the UPS
longer than 6 ? s to switch to service mode.
The red LED lights up.
?
Press and hold down both buttons on the front of the UPS
for longer than 6 ? s to register the batteries.
The bar graph flashes.
?
Remove the fuses.
?
Press and hold down both buttons on the front of the UPS
for longer than 6 ? s to exit the service mode.
The red LED extinguishes.
?
?
?
?
?
Remove the cabling of the battery blocks.
Remove the batteries.
Install new batteries.
Connect the cabling of the battery blocks.
Insert the fuses.
An exact description of the replacement procedure for all
power storage devices can be found in the corresponding
data sheet at www.phoenixcontact.net/catalog .